Construction DB | Construction Site Handbook | Air Test

Construction Site Handbook

Share your expertise and experience with the Construction DB community. You are free to add or edit any of the articles in the Construction Knowledge Collaboration Project.

[English | 简体] Air Test

This test will be set up and conducted by site supervisor and the procedures in brief are as follows : -

1. Before test , the ends of the pipeline are plugged using expanding disc stoppers and one end is connected with a U-tube manometer .
2. Air to be pumped into the pipeline until a test pressure of slightly more than 100mm of water is observed in the U-tube .
3. Allow a few minutes for stabilization of the ambient temperature , then adjust the air pressure to 100mm of water in the U-tube . Lock the device without further pumping .
4. After five-minute test period , read the pressure in the U-tube and record .
5. It is satisfactory if the air pressure remains above 75mm head of water at the end of the air test .